Cbt asme chilled water buffer tanks cbt are designed for chilled water systems with insufficient water volume capacity in relation to the chiller capacity.
Buffer tank in chilled water system.
W essels company manufactures two styles of buffer tanks.
Taco chilled hot water buffer tanks are also available with a wide range of insulation options to suit your application needs.
Cemline chilled water buffer tanks cwb are designed to be used with chillers which do not have water volumes of sufficient size in relation to the chiller.
The insufficiently sized systems do not have enough buffer capacity for the chilled water causing poor temperature control erratic system operation and excessive compressor cycling.
Subtract that number from the chiller manufacturers recommended system capacity.
I have a primary secondary system with two 70 ton air cooled screw chillers.
All amtrol buffer tanks are made in the usa at our iso 9001 2015 registered facilities.
Cemline recommends a minimum sys volume of 3 6.
Volume of total buffer tank c x v r v a ton x gal ton.
Available for chilled water and hot water applications.
If a 100 ton chiller requires 1000 gallons of system capacity for high accuracy control and the total piping system totals only 600 gallons a 400 gallon buffer tank would be required.
Taco chilled hot water buffer tanks are designed constructed and tested to asme section viii div.
The system is mainly serving fan coils units with 2 way modulating valves.
Chiller manufacturer s recommended system volume per ton v r check with chiller manufacturer for specific requirements.
Relatively low water volume systems require additional buffer capacity for the system to eliminate problems such as excessive chiller cycling poor temperature control and erratic system.
We focus solely on serving the unique needs of each customer with a product portfolio including boilers water heaters pool heaters cogeneration products and commercial package.
Do i need a buffer tank.
General question regarding buffer tanks for chilled water systems.
My total system volume is approximately 950 gals.
Typical hvac chiller systems are between 3 to 6 gallons per ton.
Chilled water buffer tanks cbt and hot water buffer tanks hbt.
While 6 to 10 gallons are used for applications in which temperature accuracy is critical.